Carrier Heat Pump: Pressure test field refrigerant piping

Updated · by Aurora Star Tech Inc.

Pressure test field refrigerant piping on a Carrier heat pump: After field piping is complete, pressure test with inert gas, then vacuum test before charging.

Homeowner with a heat pump problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Split system field piping

How to fix pressure test field refrigerant piping: step by step

  1. Pressure test the field piping with inert gas before vacuum and charging.
  2. Test the low side at the low side design pressure and the high side at the high side design pressure. If the sides cannot be isolated, test the whole system to the low side design pressure.
  3. After removing the pressure source, hold the test pressure for at least 1 hour with no drop on the gauge. Gauge resolution must not exceed 5% of the test pressure.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Carrier Heat Pump codes

Models

D5CURA + D5MUWAD5CURAH18AAKD5CURAH24AAKD5CURAH30AAKD5CURAH36AAKD5CURAH48AAKD5CURAH60AAK

Source: D5CURA installation manual, p. 4. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.