Carrier Heat Pump: Outdoor DC fan motor check (controller in outdoor PCB)
Outdoor DC fan motor check (controller in outdoor PCB) on a Carrier heat pump: Used to decide between replacing the fan motor and replacing the PCB.
Applies to: D5CURA outdoor DC fan motor
How to fix outdoor dc fan motor check (controller in outdoor pcb): step by step
- Disconnect the UVW connector.
- Measure resistance between U-V, U-W and V-W.
- If the three resistances are not equal, replace the fan motor.
- If they are equal, replace the PCB.
If the unit shows an error code, look it up: Carrier Heat Pump codes
Models
D5CURA + D5MUWAD5CURAH18AAKD5CURAH24AAKD5CURAH30AAKD5CURAH36AAKD5CURAH48AAKD5CURAH60AAK
Source: Carrier D5CURA service manual, p. 33. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.