Carrier Heat Pump: Limit buried refrigerant line length and rise
Limit buried refrigerant line length and rise on a Carrier heat pump: Buried refrigerant pipe can let refrigerant migrate to the cold buried section during shutdown, causing liquid slugging and possible compressor damage at start-up.
Applies to: D5CURA refrigerant line installation
How to fix limit buried refrigerant line length and rise: step by step
- Do not bury more than 36 in (914 mm) of refrigerant pipe.
- If any section is buried, make a vertical rise of at least 6 in (152 mm) to the outdoor unit valve connections.
If the unit shows an error code, look it up: Carrier Heat Pump codes
Models
D5CURA + D5MUWAD5CURAH18AAKD5CURAH24AAKD5CURAH30AAKD5CURAH36AAKD5CURAH48AAKD5CURAH60AAK
More commissioning tips for heat pump
Source: D5CURA service manual, p. 1. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.