Carrier Heat Pump: Evacuate refrigerant tubing and indoor coil (deep vacuum)
Evacuate refrigerant tubing and indoor coil (deep vacuum) on a Carrier heat pump: Preferred method. Use a vacuum pump that can pull down to 1/4 inch, with a gauge that reads that depth accurately.
Applies to: Refrigerant lines and indoor coil
How to fix evacuate refrigerant tubing and indoor coil (deep vacuum): step by step
- Tighten flare nuts A, B, C and D fully.
- Connect the manifold gauge charge hose to the low side service valve charge port.
- Connect the charge hose to the vacuum pump.
- Fully open the low side of the manifold gauge.
- Start the vacuum pump and evacuate to a deep vacuum.
- Fully close the low side of the manifold gauge and stop the pump.
- Disconnect the charge hose from the low side service valve.
- Fully open service valves B and A.
- Securely tighten the service valve caps.
- Break vacuum with dry nitrogen if needed. Never use the compressor as a vacuum pump.
If the unit shows an error code, look it up: Carrier Heat Pump codes
Models
D5CURA + D5MUWAD5CURAH18AAKD5CURAH24AAKD5CURAH30AAKD5CURAH36AAKD5CURAH48AAKD5CURAH60AAK
Source: D5CURA installation manual, p. 29. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.