Carrier Heat Pump: Connecting the refrigerant pipes at the units
Connecting the refrigerant pipes at the units on a Carrier heat pump: Connect the indoor unit first, then the outdoor unit, always low-pressure line first.
Applies to: Indoor and outdoor unit flare connections
Common causes of connecting the refrigerant pipes at the units
- Over-tightening can damage the flare. Under-tightening can leak.
How to fix connecting the refrigerant pipes at the units: step by step
- Connect the copper pipes to the indoor unit first.
- Connect the pipes to the outdoor unit next.
- Connect the low-pressure line first, then the high-pressure line.
- Put a thin coat of refrigeration oil on each flared end.
- Align the two pipe centres.
- Tighten the flare nut by hand.
- Hold the unit fitting with a wrench and tighten the nut to the Table 9 torque with a torque wrench.
- After indoor connection, bind the power cable, signal cable and piping together with tape.
If the unit shows an error code, look it up: Carrier Heat Pump codes
Models
D5CURA + D5MUWAD5CURAH18AAKD5CURAH24AAKD5CURAH30AAKD5CURAH36AAKD5CURAH48AAKD5CURAH60AAK
Source: Carrier D5CURA installation manual, p. 14. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.