Carrier Heat Pump: Communication wire selection (RS485)
Communication wire selection (RS485) on a Carrier heat pump: Communication wire runs up to the maximum system piping length. Stranded shielded wire is recommended. Thermostat wire can be reused only under set conditions.
Applies to: D5CURA indoor to outdoor communication
How to fix communication wire selection (rs485): step by step
- Use 16 AWG stranded shielded wire for RS485 between indoor and outdoor units; 16 to 18 AWG is allowed.
- Reuse 18 AWG thermostat wire only if it is not coiled, has no splices on the wires used, all unused wires are grounded to the ODU, it is in good condition, and no nearby EMI sources exist.
- Replace 18 AWG wire with 16 AWG stranded shielded wire if communication problems occur.
If the unit shows an error code, look it up: Carrier Heat Pump codes
Models
D5CURA + D5MUWAD5CURAH18AAKD5CURAH24AAKD5CURAH30AAKD5CURAH36AAKD5CURAH48AAKD5CURAH60AAK
More commissioning tips for heat pump
Source: D5CURA product data, p. 116. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.