Viessmann Boiler: Test the fixed high limit (FHL)
Test the fixed high limit (FHL) on a Viessmann boiler: Functional check of the fixed high limit. Boiler and burner must be watched the whole time.
Applies to: Fixed high limit
How to fix test the fixed high limit (fhl): step by step
- Deactivate low-temperature floor heating, with or without mixing valves, before starting.
- Isolate attached DHW tanks and confirm the expansion tank will take the water expansion.
- Let boiler water cool to 140 °F / 60 °C before activating any heat distribution system.
- Press and hold the FHL test switch. Never tape or otherwise hold it in place.
- The adjustable high limit is bypassed, so the burner runs until the fixed high limit trips.
- When the burner shuts off, release the test switch.
- Wait until boiler water is 27 °F / 15 °C below the selected safety temperature, then press the reset button.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
HO1BKW2Vitotronic 200, type H01BVitotronic 200, Type HO1B
More service & test modes tips for boiler
Source: Vitotronic 200 service instructions, p. 66. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.