Warming things up…Dialing in your comfort…Almost cozy…
Reliable Heating and Cooling Solutions – Quality Service, Fair Prices, Guaranteed Satisfaction!

Viessmann Boiler: Temperatures and brief scans (Vitotronic 300-K)

Updated · by Aurora Star Tech Inc.

Temperatures and brief scans (Vitotronic 300-K) on a Viessmann boiler: Shows live temperatures, outputs and states. Items shown depend on what is connected, such as sensors, DHW tank sensors, supply temperature sensor and remote control.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitotronic 300-K, MW1S

How to fix temperatures and brief scans (vitotronic 300-k): step by step

  1. Hold the flagged buttons together for about 2 seconds.
  2. Select the required scan with the up or down button.
  3. Press OK to view it.
  4. Read the outdoor temperature (actual and dampened), boiler sequence, boiler output percentage and integral, boiler temperatures 1 to 4, sensor 17A and 17B values, DHW and supply temperatures, and room temperature.
  5. To reset the dampened outdoor temperature to the actual value, use the reset button shown on the scan screen.
  6. Negative integral values mean start-up integral, positive values mean shutdown integral.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

More service & test modes tips for boiler

Source: Viessmann Vitotronic 100 GC1 / 300-K MW1S installation and service instructions, p. 91. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Emergency Boiler Repair

647-657-2977