Viessmann Boiler: Setting the DIP switch for a separate room temperature sensor
Setting the DIP switch for a separate room temperature sensor on a Viessmann boiler: When a separate room temperature sensor is connected, the matching DIP switch on the remote control PCB must be turned on. The switch differs between the two remotes.
Applies to: Vitotrol 200 and Vitotrol 300 remote controls
How to fix setting the dip switch for a separate room temperature sensor: step by step
- On Vitotrol 200, set DIP switch S6.3 to ON.
- On Vitotrol 300, set DIP switch S3.3 to ON.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
HK1BHK1MHK1SHK3SVitotrol 200Vitotrol 300
More commissioning tips for boiler
Source: Vitotronic 200-H installation and service instructions, p. 44 and p. 46. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.