Viessmann Boiler: Set the rotary dial on the 2-wire BUS communication module
Set the rotary dial on the 2-wire BUS communication module on a Viessmann boiler: The control connects to the Viessmann 2-wire BUS through a plug-in communication module. Its rotary dial sets the system version and must be unique on the bus. Position 4 is the default when a mixing valve actuator kit is used on a wall-mounted boiler, so do not duplicate it when adding a second Vitotronic 200-H.
Applies to: Vitotronic 200-H with 2-wire BUS communication module
How to fix set the rotary dial on the 2-wire bus communication module: step by step
- Plug the 2-wire BUS communication module into the control unit (accessory, see parts list).
- Set the rotary dial on the module to a system version between 4 and C.
- Make sure no other control unit on the bus uses the same rotary dial position.
- On a wall-mounted boiler with one mixing valve actuator kit, the default position is 4; when adding another Vitotronic 200-H, pick a position other than 4.
- If a boiler control unit for wall-mounted boilers or a Dekamatik system is connected, adjust the differential temperature at that control unit.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
HK1BHK1MHK1SHK3SVitotrol 200Vitotrol 300
More commissioning tips for boiler
Source: Vitotronic 200-H installation and service instructions, p. 16. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.