Viessmann Mini-Split: Manual switch test operation at the indoor unit
Manual switch test operation at the indoor unit on a Viessmann mini-split: Test the indoor unit with the manual button when the remote is not in use. Preset set point is 76°F (24°C), fan AUTO, discharge direction preset for COOL or HEAT.
Applies to: DLFSCBH / DLFLCBH indoor unit
How to fix manual switch test operation at the indoor unit: step by step
- Open the indoor unit front panel.
- Press the manual switch once to energize the unit.
- Confirm preset set point 76°F (24°C), fan speed AUTO, and discharge direction preset for the mode.
- Press the manual switch twice more to turn the unit off after the test.
If the unit shows an error code, look it up: Viessmann Mini-Split codes
More service & test modes tips for mini-split
Source: DLFSCBH and DLFLCBH installation instructions, p. 15. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.