Service & test modes: Mini-Split tips
Short, practical technician tips on service & test modes for mini-split. Check each one against the manual for your exact model before acting.
Read live data with the outdoor check button (SW1)
Carrier · DLCMRBH / DLCMHBH multi-zone outdoor units 18-48K (Midea, Carrier, Viessmann Vitocal 200-S)
Each press of SW1 steps through a value on the outdoor display.
- Press 1 = number of indoor units talking. 2 = mode (0 off, 1 fan, 2 cool, 3 heat, 4 forced cool, A forced defrost).
- Presses 17-21 = T2B per zone, 22-26 = room temp per zone, 27-31 = coil temp per zone, 32 = T3, 33 = T4, 34 = discharge temp.
- Press 45 (all sizes) = last fault or protection (00 = none). See the check switch table for the full list; the 18K board uses a slightly different order.
Run the automatic wiring / piping correction
Carrier · DLCMRBH / DLCMHBH multi-zone outdoor units 18-48K (Midea, Carrier, Viessmann Vitocal 200-S)
The outdoor unit can find and fix crossed wiring vs piping ports by itself.
- Outdoor temperature must be above 41 F (5 C). Indoor units do not need to be running.
- Hold CHECK (SW1) on the outdoor board about 6 seconds until CE shows (FA may show first, keep holding).
- Indoor units go to 76 and the compressor runs for about 5-10 minutes.
- When CE changes to 00 it is done. Set each indoor unit back with its remote (they stay at 76).
Read live data with the outdoor check button (SW1)
Midea · DLCMRBH / DLCMHBH multi-zone outdoor units 18-48K (Midea, Carrier, Viessmann Vitocal 200-S)
Each press of SW1 steps through a value on the outdoor display.
- Press 1 = number of indoor units talking. 2 = mode (0 off, 1 fan, 2 cool, 3 heat, 4 forced cool, A forced defrost).
- Presses 17-21 = T2B per zone, 22-26 = room temp per zone, 27-31 = coil temp per zone, 32 = T3, 33 = T4, 34 = discharge temp.
- Press 45 (all sizes) = last fault or protection (00 = none). See the check switch table for the full list; the 18K board uses a slightly different order.
Run the automatic wiring / piping correction
Midea · DLCMRBH / DLCMHBH multi-zone outdoor units 18-48K (Midea, Carrier, Viessmann Vitocal 200-S)
The outdoor unit can find and fix crossed wiring vs piping ports by itself.
- Outdoor temperature must be above 41 F (5 C). Indoor units do not need to be running.
- Hold CHECK (SW1) on the outdoor board about 6 seconds until CE shows (FA may show first, keep holding).
- Indoor units go to 76 and the compressor runs for about 5-10 minutes.
- When CE changes to 00 it is done. Set each indoor unit back with its remote (they stay at 76).
Read live data with the outdoor check button (SW1)
Viessmann · DLCMRBH / DLCMHBH multi-zone outdoor units 18-48K (Midea, Carrier, Viessmann Vitocal 200-S)
Each press of SW1 steps through a value on the outdoor display.
- Press 1 = number of indoor units talking. 2 = mode (0 off, 1 fan, 2 cool, 3 heat, 4 forced cool, A forced defrost).
- Presses 17-21 = T2B per zone, 22-26 = room temp per zone, 27-31 = coil temp per zone, 32 = T3, 33 = T4, 34 = discharge temp.
- Press 45 (all sizes) = last fault or protection (00 = none). See the check switch table for the full list; the 18K board uses a slightly different order.
Run the automatic wiring / piping correction
Viessmann · DLCMRBH / DLCMHBH multi-zone outdoor units 18-48K (Midea, Carrier, Viessmann Vitocal 200-S)
The outdoor unit can find and fix crossed wiring vs piping ports by itself.
- Outdoor temperature must be above 41 F (5 C). Indoor units do not need to be running.
- Hold CHECK (SW1) on the outdoor board about 6 seconds until CE shows (FA may show first, keep holding).
- Indoor units go to 76 and the compressor runs for about 5-10 minutes.
- When CE changes to 00 it is done. Set each indoor unit back with its remote (they stay at 76).
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.