Viessmann Mini-Split: Enter and exit Inquiry Mode on the remote
Enter and exit Inquiry Mode on the remote on a Viessmann mini-split: Inquiry Mode shows live unit readings on the indoor unit display. The remote stays in this mode for 1 minute with no button press. Each code from 0 to 30 is selected with the UP or DOWN arrow. Press OK to send the value to the indoor unit as well.
Applies to: DLCSRB outdoor units with remote control
How to fix enter and exit inquiry mode on the remote: step by step
- Press and hold the On/Off and Fan buttons together for 8 seconds to enter Inquiry Mode.
- Press UP or DOWN to step through codes 0 to 30. Wait about 1 second for the reading to show on the indoor display.
- Press and hold On/Off and Fan together for 2 seconds to exit.
If the unit shows an error code, look it up: Viessmann Mini-Split codes
Models
36AAK48AAK58AAK80ES(N,L)80ESUDLCURAH18AAKDLCURAH18ABKDLCURAH24AAKDLCURAH24ABKDLCURAH30AAKDLCURAH30ABKDLCURAH36AAKDLCURAH36ABKDLCURAH48AAKDLCURAH48ABKDLCURAH60AAKDLCURAH60ABKFEM4FVM4X48***LFVM4X60***LFXM4X48**ALFXM4X60**AL
More service & test modes tips for mini-split
Source: DLCSRB service manual, p. 24. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.