Carrier Mini-Split: Outdoor to indoor power and communication wiring
Outdoor to indoor power and communication wiring on a Carrier mini-split: Power and communication run between the outdoor and indoor units. Stranded copper with 600 V insulation is required. A shielded cable can replace the signal conductors in high EMF areas.
Applies to: D5FSFAH 9K to 16K
How to fix outdoor to indoor power and communication wiring: step by step
- Size wires per NEC or CEC and local codes, using the MCA and MOCP values from the electrical data table.
- Use 14/3 stranded wire with ground, 600 V rated, for power and communication from outdoor to indoor unit.
- Connect L1 to terminal 1, N or L2 to terminal 2, and communication to terminal 3; land the green ground wire on the ground terminal.
- In high EMF areas with communication problems, use 14/2 stranded shielded wire for terminals 2 and 3 (polarity sensitive). Land the shield on ground at the outdoor unit only.
- Keep wires clear of refrigerant tubing, the compressor and moving parts, and tighten every connection.
If the unit shows an error code, look it up: Carrier Mini-Split codes
Models
D5FSFAH09XAKD5FSFAH12XAKD5FSFAH16XAK
More commissioning tips for mini-split
Source: D5FSFAH service manual, p. 10. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.