Carrier Mini-Split: Leak test indoor field joints
Leak test indoor field joints on a Carrier mini-split: Field-made joints inside the building must be tested for tightness with a sensitivity of 5 g/year of refrigerant or better.
Applies to: Indoor field joints
How to fix leak test indoor field joints: step by step
- Test at a pressure of at least 0.25 times the maximum allowable pressure.
- Confirm no leak is detected.
- Do not use detachable joints on the indoor side. Brazed or welded joints are acceptable.
If the unit shows an error code, look it up: Carrier Mini-Split codes
Models
D5FCFAH18XAKD5FCFAH24XAKD5FCFAH36XAKD5FCFAH48XAKD5FCFAH58XAKD5FCFH18XAKD5FCFH24XAKD5FCFH36XAKD5FCFH48XAKD5FCFH58XAKD5SCHA
More commissioning tips for mini-split
Source: Carrier D5FCFAH service manual, p. 4-5. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.