Carrier Mini-Split: Evacuation check after pulling vacuum
Evacuation check after pulling vacuum on a Carrier mini-split: The system must reach the required vacuum before it is checked for holding. The vacuum target is the lower of 500 microns or the level required by local code.
Applies to: Split system field piping
How to fix evacuation check after pulling vacuum: step by step
- Pull the system down to the specified vacuum level or lower.
- Isolate the system from the vacuum pump.
- Confirm the pressure does not rise above 1500 microns within 10 minutes.
If the unit shows an error code, look it up: Carrier Mini-Split codes
Models
D5FCFAH18XAKD5FCFAH24XAKD5FCFAH36XAKD5FCFAH48XAKD5FCFAH58XAKD5FCFH18XAKD5FCFH24XAKD5FCFH36XAKD5FCFH48XAKD5FCFH58XAKD5SCHA
More commissioning tips for mini-split
Source: Carrier D5FCFAH service manual, p. 5. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.