Carrier Mini-Split: Charging and recharging requirements for flammable refrigerant
Charging and recharging requirements for flammable refrigerant on a Carrier mini-split: Follow normal charging practice plus the flammable refrigerant rules. Avoid overfilling. The system must be leak tested after charging and again before leaving the site.
Applies to: D5FSOAH systems using flammable refrigerant
How to fix charging and recharging requirements for flammable refrigerant: step by step
- Use only tools rated for flammable refrigerant, and keep hoses as short as possible.
- Keep refrigerant cylinders upright and make sure the system is earthed before charging.
- Before recharging, pressure test with oxygen-free nitrogen (OFN).
- Do not charge refrigerant into a system that is not clean and checked. Never use compressed air or oxygen for purging.
- Label the system once charging is complete.
- Carry out a leak test after charging and before commissioning, and repeat it before leaving the site.
If the unit shows an error code, look it up: Carrier Mini-Split codes
Models
D5FSOAH06XAKD5FSOAH12XAKD5FSOAH18XAK
More commissioning tips for mini-split
Source: Carrier D5FSOAH service manual, p. 6-7. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.