Viessmann Heat Pump: Remove main control board and fan capacitors (48K-58K electrical parts)
Remove main control board and fan capacitors (48K-58K electrical parts) on a Viessmann heat pump: Electrical parts removal for 48K to 58K sizes. Low and high pressure switch, T3 and T4 sensors connect to the IPM module. TP connects to the indoor unit.
Applies to: 48K-58K
How to fix remove main control board and fan capacitors (48k-58k electrical parts): step by step
- Remove the 2 screws and disconnect the power supply wires.
- Remove the 3 screws and disconnect the ground wires.
- Disconnect the wires connected to the main control board.
- Disconnect the wires between the main control board and the IPM module board.
- Remove the 4 screws, release the 6 hooks, and remove the main control board.
- Remove 1 screw per fan motor capacitor and remove the capacitors.
If the unit shows an error code, look it up: Viessmann Heat Pump codes
Models
06AAK09AAK12AAJ12AAK18AAK24AAK30AAKDLCLRCQ36AA3DLCLRCQ48AA3DLCLRCQ58AA3DLCURAQ18AA3DLCURAQ18AB3DLCURAQ24AA3DLCURAQ24AB3DLCURAQ30AA3DLCURAQ30AB3DLCURAQ36AA3DLCURAQ36AB3DLCURAQ48AA3DLCURAQ48AB3DLCURAQ60AA3DLCURAQ60AB3
Source: DLCLRC service manual, p. 48. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.