Viessmann Heat Pump: Inverter power module (IPM) continuity check
Inverter power module (IPM) continuity check on a Viessmann heat pump: Checks the IPM board for shorts or faults between the P, N, U, V and W terminals. The manual gives the expected reading as several megaohms.
Applies to: DLCSRB outdoor units
How to fix inverter power module (ipm) continuity check: step by step
- Turn off the outdoor unit and disconnect the power supply.
- Discharge the electrolytic capacitors and confirm all stored energy is gone.
- Disassemble the outdoor PCB or the IPM board.
- With a digital tester in diode/resistance mode, measure between P and U, V, W, N.
- Measure between U, V, W and N.
- Replace the module if the readings are not several megaohms.
If the unit shows an error code, look it up: Viessmann Heat Pump codes
Models
06AAK09AAK12AAJ12AAK18AAK24AAK30AAKDLCLRCQ36AA3DLCLRCQ48AA3DLCLRCQ58AA3DLCURAQ18AA3DLCURAQ18AB3DLCURAQ24AA3DLCURAQ24AB3DLCURAQ30AA3DLCURAQ30AB3DLCURAQ36AA3DLCURAQ36AB3DLCURAQ48AA3DLCURAQ48AB3DLCURAQ60AA3DLCURAQ60AB3
Source: DLCSRB Service Manual, p. 50. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.