Warming things up…Dialing in your comfort…Almost cozy…
Reliable Heating and Cooling Solutions – Quality Service, Fair Prices, Guaranteed Satisfaction!

Viessmann Heat Pump: Evacuating and charging the refrigerant system

Updated · by Aurora Star Tech Inc.

Evacuating and charging the refrigerant system on a Viessmann heat pump: Deep vacuum method to remove air and moisture from the refrigerant tubes and indoor coil. Target is 500 microns. Always break vacuum with dry nitrogen. Never use the compressor as a vacuum pump.

Homeowner with a heat pump problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: DLCURA outdoor units with indoor coil and refrigerant tubing

How to fix evacuating and charging the refrigerant system: step by step

  1. Tighten all flare nuts fully. Connect the manifold gauge charge hose to the charge port of the low side service valve.
  2. Connect the charge hose to the vacuum pump.
  3. Fully open the low side of the manifold gauge.
  4. Start the vacuum pump and evacuate using the triple evacuation method.
  5. When evacuation is complete, fully close the low side of the gauge and stop the pump.
  6. Disconnect the charge hose from the low side service valve charge port.
  7. Fully open service valves B and A.
  8. Tighten the valve caps securely.
  9. If line length is over 25 ft (8 m), add refrigerant as specified in the piping table.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Heat Pump codes

Models

06AAK09AAK12AAJ12AAK18AAK24AAK30AAKDLCLRCQ36AA3DLCLRCQ48AA3DLCLRCQ58AA3DLCURAQ18AA3DLCURAQ18AB3DLCURAQ24AA3DLCURAQ24AB3DLCURAQ30AA3DLCURAQ30AB3DLCURAQ36AA3DLCURAQ36AB3DLCURAQ48AA3DLCURAQ48AB3DLCURAQ60AA3DLCURAQ60AB3

Source: DLCURA Service Manual, p. 17. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.