Viessmann Heat Pump: Evacuate and charge the refrigerant system
Evacuate and charge the refrigerant system on a Viessmann heat pump: Deep vacuum procedure with triple evacuation. Use a vacuum pump that reaches 500 microns and a gauge that reads accurately at that level. Never use the compressor as a vacuum pump.
Applies to: DLCSRB outdoor units, all sizes
How to fix evacuate and charge the refrigerant system: step by step
- Tighten all flare nuts fully and connect the manifold charge hose to the low side service port.
- Connect the other charge hose to the vacuum pump.
- Fully open the low side of the manifold gauge.
- Start the pump and evacuate to 500 microns, then run it 15 more minutes.
- Close the service valves and shut off the pump.
- Break the vacuum with dry nitrogen to 2 psig, then hold 10 minutes so the nitrogen absorbs moisture.
- Repeat the evacuation and nitrogen steps as shown in the triple evacuation chart.
- After the final evacuation, fully close the low side gauge and stop the pump.
- Add refrigerant per Table 10 if line length is over 25 ft (8 m).
- Disconnect the charge hose from the low side port.
- Fully open service valves B and A.
- Tighten all service valve caps.
If the unit shows an error code, look it up: Viessmann Heat Pump codes
Models
06AAK09AAK12AAJ12AAK18AAK24AAK30AAKDLCLRCQ36AA3DLCLRCQ48AA3DLCLRCQ58AA3DLCURAQ18AA3DLCURAQ18AB3DLCURAQ24AA3DLCURAQ24AB3DLCURAQ30AA3DLCURAQ30AB3DLCURAQ36AA3DLCURAQ36AB3DLCURAQ48AA3DLCURAQ48AB3DLCURAQ60AA3DLCURAQ60AB3
Source: DLCSRB Service Manual, p. 17. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.