Viessmann Heat Pump: Enquiry display: fan speed, EXV opening, running time, stop causes
Enquiry display: fan speed, EXV opening, running time, stop causes on a Viessmann heat pump: Other enquiry items shown on the service display, with the conversion rules.
Applies to: DLCLRC enquiry mode
How to fix enquiry display: fan speed, exv opening, running time, stop causes: step by step
- Fan speed display 0 = OFF, 1 = low, 2 = medium, 3 = high, 4 = turbo for some large motors.
- For some small motors the display is 14 to FF (hex) and the fan speed range is 200 to 2550 RPM.
- Actual fan RPM = display value converted to decimal, then multiplied by 10.
- EXV opening: actual value = display value converted to decimal, then multiplied by 2.
- Compressor continuous running time shows 0 to 255 minutes.
- Compressor stop cause shows 0 to 99 in decimal. Consult the engineering reference for the meaning.
If the unit shows an error code, look it up: Viessmann Heat Pump codes
Models
06AAK09AAK12AAJ12AAK18AAK24AAK30AAKDLCLRCQ36AA3DLCLRCQ48AA3DLCLRCQ58AA3DLCURAQ18AA3DLCURAQ18AB3DLCURAQ24AA3DLCURAQ24AB3DLCURAQ30AA3DLCURAQ30AB3DLCURAQ36AA3DLCURAQ36AB3DLCURAQ48AA3DLCURAQ48AB3DLCURAQ60AA3DLCURAQ60AB3
Source: Vitocal 100-S DLCLRC service instructions, p. 14. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.