Viessmann Heat Pump: Deep vacuum evacuation with a vacuum pump
Deep vacuum evacuation with a vacuum pump on a Viessmann heat pump: Evacuate the refrigerant tubes and indoor coil to a deep vacuum to remove air and moisture before charging.
Applies to: DLCLRC outdoor units with R410A
How to fix deep vacuum evacuation with a vacuum pump: step by step
- Tighten all flare nuts fully.
- Fully open all service valves.
- Connect the manifold charge hose to the charge port of the low side master service valve so all circuits evacuate together.
- Connect the charge hose to the vacuum pump.
- Fully open the low side of the manifold gauge.
- Start the vacuum pump and pull down to 500 microns.
- Close the low side of the manifold gauge and stop the pump once evacuation is complete.
- Disconnect the charge hose from the low side service valve charge port.
- Tighten the service valve caps securely.
If the unit shows an error code, look it up: Viessmann Heat Pump codes
Models
06AAK09AAK12AAJ12AAK18AAK24AAK30AAKDLCLRCQ36AA3DLCLRCQ48AA3DLCLRCQ58AA3DLCURAQ18AA3DLCURAQ18AB3DLCURAQ24AA3DLCURAQ24AB3DLCURAQ30AA3DLCURAQ30AB3DLCURAQ36AA3DLCURAQ36AB3DLCURAQ48AA3DLCURAQ48AB3DLCURAQ60AA3DLCURAQ60AB3
Source: Vitocal 100-S DLCLRC service instructions, p. 9. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.