Viessmann Heat Pump: Condenser high temperature protection (T3)
Condenser high temperature protection (T3) on a Viessmann heat pump: Compressor frequency is limited when the condenser coil temperature gets high.
Applies to: DLCLRC
Common causes of condenser high temperature protection (t3)
- Condenser coil temperature T3 too high
How to fix condenser high temperature protection (t3): step by step
- If T3 is between 131°F and 140°F (55°C to 60°C), the compressor drops to the lower level until F1 and then runs at F1.
- If T3 falls below 129.2°F (54°C), the compressor holds the current frequency.
- If T3 is below 125.6°F (52°C), the frequency limit is removed and the previous frequency resumes.
- If T3 is above 140°F (60°C) for 5 seconds, the compressor stops until T3 falls below 125.6°F (52°C).
If the unit shows an error code, look it up: Viessmann Heat Pump codes
Models
06AAK09AAK12AAJ12AAK18AAK24AAK30AAKDLCLRCQ36AA3DLCLRCQ48AA3DLCLRCQ58AA3DLCURAQ18AA3DLCURAQ18AB3DLCURAQ24AA3DLCURAQ24AB3DLCURAQ30AA3DLCURAQ30AB3DLCURAQ36AA3DLCURAQ36AB3DLCURAQ48AA3DLCURAQ48AB3DLCURAQ60AA3DLCURAQ60AB3
Source: Vitocal 100-S DLCLRC service instructions, p. 10. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.