Viessmann Heat Pump: Compressor protection trips
Compressor protection trips on a Viessmann heat pump: Protection functions that stop the compressor or unit. No code is listed on these pages for most of them.
Applies to: DLCSRB outdoor units
Common causes of compressor protection trips
- Compressor discharge temperature above 239°F (115°C) for 5 s
- Compressor high temperature cutout open
- Current above the set value
- Inverter module fault on current, voltage or temperature
- Zero crossing signal outside 6 to 13 ms for 240 s
How to fix compressor protection trips: step by step
- Check that the unit restarts after the cutout closes or the fault clears.
- Wait for the 3 min restart delay before retesting.
- For an inverter fault, the matching code shows on the indoor unit display.
If the unit shows an error code, look it up: Viessmann Heat Pump codes
Models
06AAK09AAK12AAJ12AAK18AAK24AAK30AAKDLCLRCQ36AA3DLCLRCQ48AA3DLCLRCQ58AA3DLCURAQ18AA3DLCURAQ18AB3DLCURAQ24AA3DLCURAQ24AB3DLCURAQ30AA3DLCURAQ30AB3DLCURAQ36AA3DLCURAQ36AB3DLCURAQ48AA3DLCURAQ48AB3DLCURAQ60AA3DLCURAQ60AB3
Source: DLCSRB Service Manual, p. 18-19. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.