Viessmann Heat Pump: Buried refrigerant line limits and tubing check
Buried refrigerant line limits and tubing check on a Viessmann heat pump: Limits for buried line runs and checks before charging the system.
Applies to: DLCSRB outdoor units, all sizes
How to fix buried refrigerant line limits and tubing check: step by step
- Do not bury more than 36 in (914 mm) of refrigerant line.
- If any line is buried, give it a minimum 6 in (152 mm) vertical rise to the outdoor service valves.
- Check that factory tubing has not shifted in shipping.
- Check that tubes do not rub each other or sheet metal.
- Check that the wire ties on the feeder tubes are secure and tight.
If the unit shows an error code, look it up: Viessmann Heat Pump codes
Models
06AAK09AAK12AAJ12AAK18AAK24AAK30AAKDLCLRCQ36AA3DLCLRCQ48AA3DLCLRCQ58AA3DLCURAQ18AA3DLCURAQ18AB3DLCURAQ24AA3DLCURAQ24AB3DLCURAQ30AA3DLCURAQ30AB3DLCURAQ36AA3DLCURAQ36AB3DLCURAQ48AA3DLCURAQ48AB3DLCURAQ60AA3DLCURAQ60AB3
More commissioning tips for heat pump
Source: DLCSRB Service Manual, p. 2, 16-17. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.