Viessmann Heat Pump: Buried refrigerant line length and rise limits
Buried refrigerant line length and rise limits on a Viessmann heat pump: Buried refrigerant pipe must stay within the maximum buried length. Without the required vertical rise, refrigerant can migrate to the cold buried section while the system is off.
Applies to: DLCSRB outdoor units, sizes 06 to 36
Common causes of buried refrigerant line length and rise limits
- Buried refrigerant pipe longer than 36 in.
- No vertical rise at the buried section to the outdoor unit valve connections
- Refrigerant migrating to the cold buried section during long shutdowns
How to fix buried refrigerant line length and rise limits: step by step
- Limit buried refrigerant pipe to 36 in. (914 mm) maximum.
- If any pipe is buried, provide a 6 in. (152 mm) vertical rise to the outdoor unit valve connections.
- Check for refrigerant slugging and compressor damage at start-up if the limits were exceeded.
If the unit shows an error code, look it up: Viessmann Heat Pump codes
Models
06AAK09AAK12AAJ12AAK18AAK24AAK30AAKDLCLRCQ36AA3DLCLRCQ48AA3DLCLRCQ58AA3DLCURAQ18AA3DLCURAQ18AB3DLCURAQ24AA3DLCURAQ24AB3DLCURAQ30AA3DLCURAQ30AB3DLCURAQ36AA3DLCURAQ36AB3DLCURAQ48AA3DLCURAQ48AB3DLCURAQ60AA3DLCURAQ60AB3
Source: DLCSRB Service Manual, p. 2. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.