Carrier Heat Pump: Refrigerant removal, purging and recovery on flammable systems
Refrigerant removal, purging and recovery on flammable systems on a Carrier heat pump: Sequence for breaking into the refrigerant circuit on a flammable refrigerant unit, and for decommissioning.
Applies to: D5FSFAH floor console ductless heat pump
How to fix refrigerant removal, purging and recovery on flammable systems: step by step
- Isolate the system electrically before starting.
- Remove the refrigerant safely under local and national rules. Recover it into correct recovery cylinders if venting is not allowed.
- Evacuate the circuit.
- Purge the circuit with oxygen-free nitrogen. Do not use compressed air or oxygen.
- Break the vacuum with oxygen-free nitrogen, fill to working pressure, vent to atmosphere, then pull a vacuum again. Repeat until no refrigerant remains.
- Vent the system to atmospheric pressure before opening the circuit.
- Use only recovery cylinders labeled for that refrigerant, and do not fill them above 80% liquid volume.
- Do not charge recovered refrigerant into another system unless it has been cleaned and checked.
- When decommissioning, label the equipment as emptied of refrigerant, dated and signed, and label it as containing flammable refrigerant.
If the unit shows an error code, look it up: Carrier Heat Pump codes
Source: D5FSFAH service manual, p. 6-7. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.