Carrier Heat Pump: Limit on buried refrigerant pipe
Limit on buried refrigerant pipe on a Carrier heat pump: Buried refrigerant pipe must stay within limits. Refrigerant can migrate into a cold buried section and slug the compressor at start-up.
Applies to: D5FSFAH floor console ductless heat pump
How to fix limit on buried refrigerant pipe: step by step
- Do not bury more than 36 in. (914 mm) of refrigerant pipe.
- If any section is buried, give it a vertical rise of at least 6 in. (152 mm) to the outdoor unit valve connections.
If the unit shows an error code, look it up: Carrier Heat Pump codes
More commissioning tips for heat pump
Source: D5FSFAH service manual, p. 1. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.