Viessmann Air Handler: Choose the control method
Choose the control method on a Viessmann air handler: Scenario 1 uses the wired controller KSACN1001AAA (non-polarity, has an infrared receiver that works with the remote). The included wireless remote gives the same functions and can be used with the wired controller. Both need SW1-1 in the OFF position (default). Scenario 2 uses a third-party heat pump thermostat through the built-in 24V interface, which needs SW1-1 in the ON position.
Applies to: DLFSAB / DLFLAB
How to fix choose the control method: step by step
- For wired or wireless controller control, set SW1-1 to OFF (default).
- For third-party 24V heat pump thermostat control, set SW1-1 to ON.
- Connect the wired controller KSACN1001AAA if used; it is non-polarity.
If the unit shows an error code, look it up: Viessmann Air Handler codes
Models
DLFLABH36XA3DLFLABH48XA3DLFLABH60XA3DLFSABH18XB3DLFSABH24XB3DLFSABH30XB3DLFSABH36XB3DLFUAAQ18XB3DLFUAAQ24XB3DLFUAAQ30XB3DLFUAAQ36XA3DLFUAAQ36XB3DLFUAAQ48XA3DLFUAAQ60XA3
More commissioning tips for air handler
Source: Vitocal IND-A DLFSAB/DLFLAB service manual, p. 10. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.