Carrier Air Handler: Select location: separation, grounding and return air
Select location: separation, grounding and return air on a Carrier air handler: Location rules for the indoor unit, including return air and garage installs.
Applies to: Indoor air handler
How to fix select location: separation, grounding and return air: step by step
- Keep indoor and outdoor units, cables and wires at least 1 m (3-1/5 ft) from televisions or radios to avoid static or image distortion. This may not be enough for some appliances.
- Electrically ground the indoor unit per national and local electrical code.
- Mount on a structure that can support the unit weight.
- Do not install in a moist environment; moisture corrodes parts and can cause shorts.
- Do not install where there are corrosive gases, oil drilling, coastal salt, strong electromagnetic waves, or stored flammable materials or gas.
- For a garage installation, place the heating elements at least 18 in (46 cm) above the floor.
- Make an airtight seal between the bottom of the air handler and the return air plenum using fiberglass strips, foil tape, caulking or an equal method.
- Do not draw return air from a room with a gas appliance, water heater, or carbon-monoxide-producing device such as a wood fireplace.
If the unit shows an error code, look it up: Carrier Air Handler codes
Source: Carrier D5FSAAH / D5FLAAH installation manual, p. 15. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.