Carrier Air Handler: Return air seal and return air source
Return air seal and return air source on a Carrier air handler: The return air connection must be airtight and must not pull air from a room with a gas appliance or a combustion source.
Applies to: D5FSAA / D5FLAA air handler
How to fix return air seal and return air source: step by step
- Seal the bottom of the air handler to the return air plenum with fiberglass strips, foil tape, caulk or an equivalent seal.
- Do not draw return air from a room that contains the air handler or any gas-fired appliance, such as a water heater, or a carbon monoxide source, such as a wood fireplace.
- Locate the return intake away from heat sources and warm or cool air sources that could change the sensed return air temperature.
- If return air is ducted, install the duct flush with the floor and set the unit over the opening so all return air passes through the coil.
If the unit shows an error code, look it up: Carrier Air Handler codes
Source: Carrier D5FSAA/D5FLAA installation manual, p. 16. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.