Carrier Air Handler: Refrigerant removal, purging and evacuation
Refrigerant removal, purging and evacuation on a Carrier air handler: Order of steps when breaking into the refrigerant circuit on a flammable refrigerant unit.
Applies to: D5FUHAQ refrigerant circuit
How to fix refrigerant removal, purging and evacuation: step by step
- Safely remove the refrigerant following local and national rules and recover it into correct recovery cylinders.
- Evacuate the circuit.
- Purge the circuit with oxygen-free nitrogen.
- Evacuate again.
- Flush or purge with nitrogen continuously when using flame to open the circuit, then open the circuit.
- Never use compressed air or oxygen for purging.
- Keep the vacuum pump outlet away from ignition sources and make sure there is ventilation.
- Repeat the nitrogen purge until no refrigerant remains, then vent to atmospheric pressure before work.
If the unit shows an error code, look it up: Carrier Air Handler codes
Source: D5FUHAQ Owner's Manual, p. 5. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.