Carrier Air Handler: Refrigerant recovery and decommissioning
Refrigerant recovery and decommissioning on a Carrier air handler: Steps for removing refrigerant before service or disposal on a flammable refrigerant system.
Applies to: R454B systems being serviced or decommissioned
How to fix refrigerant recovery and decommissioning: step by step
- Isolate the system electrically and confirm electrical power is available before starting.
- Pump down the system if possible. If a vacuum is not possible, use a manifold to remove refrigerant from several points.
- Use recovery equipment and cylinders rated for flammable refrigerant, with a calibrated scale to check the cylinder weight.
- Do not fill cylinders above 80% liquid volume or exceed their maximum working pressure.
- Do not mix refrigerants in recovery units or cylinders.
- Purge with oxygen-free nitrogen only. Never use compressed air or oxygen.
- Label the equipment as decommissioned and as containing flammable refrigerant.
If the unit shows an error code, look it up: Carrier Air Handler codes
Source: Carrier D5FS(L)AAH owner's manual, pp. 6-7. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.