Warming things up…Dialing in your comfort…Almost cozy…
Reliable Heating and Cooling Solutions – Quality Service, Fair Prices, Guaranteed Satisfaction!

Carrier Air Handler: Leak detection and refrigerant removal for flammable refrigerant

Updated · by Aurora Star Tech Inc.

Leak detection and refrigerant removal for flammable refrigerant on a Carrier air handler: Leak check and removal method when opening the circuit.

Homeowner with a air handler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Indoor and outdoor units using flammable refrigerant

How to fix leak detection and refrigerant removal for flammable refrigerant: step by step

  1. Never use a halide torch or any naked flame to search for leaks.
  2. Electronic detectors can be used, but sensitivity may need re-calibration for flammable refrigerant. Calibrate in a refrigerant-free area.
  3. Use leak detection fluid, but avoid chlorine-based detergents that can corrode copper.
  4. If a leak needs brazing, remove all refrigerant or isolate the leaking section with shut-off valves first.
  5. Remove the refrigerant per local rules and evacuate.
  6. Purge with oxygen-free nitrogen (never compressed air or oxygen), repeat as needed, then vent to atmospheric pressure before opening the circuit.
  7. Keep vacuum pump outlet away from ignition sources and make sure there is ventilation.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Carrier Air Handler codes

Source: Carrier D5FSAAH / D5FLAAH installation manual, p. 8-9. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.