Carrier Air Handler: Leak check with dry nitrogen
Leak check with dry nitrogen on a Carrier air handler: Pressure test the piping before evacuation. Use dry nitrogen only. Never use air or oxygen-containing gases for leak testing.
Applies to: D5FUHA piping
How to fix leak check with dry nitrogen: step by step
- Pressurize the system with dry nitrogen to 500 psig.
- Do not exceed 550 psi.
- Hold the pressure for at least 30 minutes.
- Record YES or NO on the start-up checklist.
If the unit shows an error code, look it up: Carrier Air Handler codes
Models
D5FUHAH24AAKD5FUHAH36AAKD5FUHAH60AAKEHKMD05KNEHKMD08KNEHKMD10KNEHKMD15KNEHKMD20KNEHKMD25KN
More commissioning tips for air handler
Source: D5FUHA Installation Instructions, p. 69. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.