Carrier Air Handler: Leak check and evacuation for start-up
Leak check and evacuation for start-up on a Carrier air handler: Pressure test the piping with dry nitrogen. Never use air or oxygen-containing gases for leak testing. Evacuation can use the Triple Evacuation Method or the Deep Vacuum Method.
Applies to: D5FUAA refrigerant piping start-up
How to fix leak check and evacuation for start-up: step by step
- Hold the system at 500 psig (max. 550 psi) for a minimum of 30 minutes using dry nitrogen.
- Evacuate by the Triple Evacuation Method or the Deep Vacuum Method as outlined in the manual.
- Confirm the system holds 500 microns for 1 hour.
- Confirm the line set diameter matches the evaporator connections.
- For conventional fan coils, confirm the line set matches the outdoor unit size.
- Measure the liquid line length, calculate the additional charge, and record the final charge amount.
If the unit shows an error code, look it up: Carrier Air Handler codes
Models
45MUAAQ18XX345MUAAQ24XX345MUAAQ30XX345MUAAQ36XX345MUAAQ48XX345MUAAQ60XX3D5FUAA
More commissioning tips for air handler
Source: Carrier D5FUAA installation instructions, p. 63. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.