Carrier Air Handler: Indoor refrigerant joint leak test

Updated · by Aurora Star Tech Inc.

Indoor refrigerant joint leak test on a Carrier air handler: Field-made joints indoors must be leak tested with a method sensitive to 5 g/year of refrigerant or better, at a pressure of at least 0.25 times the maximum allowable pressure. No leak may be detected. Detachable joints are not allowed on the indoor side; brazed or welded joints are acceptable.

Homeowner with a air handler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Indoor refrigerant joints

How to fix indoor refrigerant joint leak test: step by step

  1. Use a leak detector rated 5 g/year or better.
  2. Test at a pressure of at least 0.25 times maximum allowable pressure.
  3. Confirm no leak is detected.
  4. Do not use detachable joints on the indoor side.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Carrier Air Handler codes

Models

D5FUHAH24AAKD5FUHAH36AAKD5FUHAH60AAKEHKMD05KNEHKMD08KNEHKMD10KNEHKMD15KNEHKMD20KNEHKMD25KN

More commissioning tips for air handler

Source: Carrier D5FUHA service manual, p. 4 and p. 5. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.