Carrier Air Handler: Field pipe pressure test
Field pipe pressure test on a Carrier air handler: After field piping, pressure test with inert gas, then vacuum test before charging. The test pressure must hold for at least 1 hour with no drop on the gauge. Gauge resolution must not exceed 5% of test pressure. Low side is tested to low side design pressure; high side to high side design pressure. If the sides cannot be isolated, test the whole system to the low side design pressure.
Applies to: Split system field refrigerant piping
How to fix field pipe pressure test: step by step
- Pressure test field piping with inert gas (never air or oxygen).
- Hold the test pressure for at least 1 hour.
- Confirm no pressure drop on a gauge with resolution of 5% of test pressure or better.
- Use low side design pressure for the low side and high side design pressure for the high side, or the low side pressure for the whole system if sides cannot be isolated.
If the unit shows an error code, look it up: Carrier Air Handler codes
Models
D5FUHAH24AAKD5FUHAH36AAKD5FUHAH60AAKEHKMD05KNEHKMD08KNEHKMD10KNEHKMD15KNEHKMD20KNEHKMD25KN
More commissioning tips for air handler
Source: Carrier D5FUHA service manual, p. 5. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.