Carrier Air Handler: Evacuation requirements
Evacuation requirements on a Carrier air handler: Evacuate with the triple evacuation or the deep vacuum method as written in the installation manual.
Applies to: D5FUHA piping
How to fix evacuation requirements: step by step
- Use either the triple evacuation method or the deep vacuum method.
- Pull the system down to 500 microns.
- Hold 500 microns for 1 hour.
- Record the method used on the start-up checklist.
If the unit shows an error code, look it up: Carrier Air Handler codes
Models
D5FUHAH24AAKD5FUHAH36AAKD5FUHAH60AAKEHKMD05KNEHKMD08KNEHKMD10KNEHKMD15KNEHKMD20KNEHKMD25KN
More commissioning tips for air handler
Source: D5FUHA Installation Instructions, p. 69. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.