Updated · by Aurora Star Tech Inc.

Enter engineering mode to set air volume on a Carrier air handler: Engineering mode is used to set the fan airflow for cooling and heating separately. Cooling airflow is stored in channel 23 and heating airflow in channel 25.

Homeowner with a air handler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: D5FSAA all sizes (18K to 60K)

How to fix enter engineering mode to set air volume: step by step

  1. With the unit powered on or in standby, and the controls not locked, press and hold ON/OFF + Air Speed together for 7 seconds.
  2. Select channel 23 to set the cooling airflow, or channel 25 to set the heating airflow.
  3. Pick the CFM value from the matching airflow table for the unit size, speed and offset.
  4. Check the airflow after the change against the table for that size.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Carrier Air Handler codes

More service & test modes tips for air handler

Source: D5FSAA product data, p. 24. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.