Carrier Air Handler: Check drain pan opening and install traps
Check drain pan opening and install traps on a Carrier air handler: Blower-draw units pull air through the coil, so traps are needed to stop air being drawn in through the drain lines.
Applies to: D5FSAA / D5FLAA air handler
How to fix check drain pan opening and install traps: step by step
- After removing the drain pan plug(s), check that each drain hole is fully open and clear of debris.
- Confirm no debris has fallen into the drain pan during installation.
- Install traps in the primary and auxiliary condensate drain lines (if used) on units where the blower draws air through the coil.
If the unit shows an error code, look it up: Carrier Air Handler codes
Source: Carrier D5FSAA/D5FLAA installation manual, p. 23. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.