Carrier Air Handler: Change fan airflow through CODE 23 and CODE 25
Change fan airflow through CODE 23 and CODE 25 on a Carrier air handler: Airflow is set in SERVICE mode by choosing a fan step. Code 23 sets the cooling fan speed and code 25 sets the heating fan speed.
Applies to: 18K, 24K, 30K and 36K air handler sizes, cooling and heating
How to fix change fan airflow through code 23 and code 25: step by step
- Enter SERVICE mode from INQUIRY mode as described for the remote service set-up.
- Scroll to CODE 23 for cooling fan speed, or CODE 25 for heating fan speed.
- Choose the step from the fan performance table for the unit size and mode (Default, -1 to -40, or +1 to +20).
- Check the CFM value in the table for the chosen fan speed (TURBO, HIGH, MIDDLE or LOW) at the external static pressure of the installation.
- Exit and power cycle the outdoor unit for 3 minutes to lock in the change.
If the unit shows an error code, look it up: Carrier Air Handler codes
More service & test modes tips for air handler
Source: Carrier D5FSAA/D5FLAA installation instructions, p. 36. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.