Carrier Air Handler: Bending copper refrigerant tubing
Bending copper refrigerant tubing on a Carrier air handler: Bends must use a properly sized tubing bender to avoid kinking. Minimum bend radius is 3.9 in (100 mm) at the middle of the tube. Do not bend more than 90 degrees or more than 3 times in one place.
Applies to: D5FUHA field copper lines
Common causes of bending copper refrigerant tubing
- Kinking or flattening the tube restricts flow and can damage it
How to fix bending copper refrigerant tubing: step by step
- Use a tubing bender sized for the line.
- Keep the bend radius at least 3.9 in (100 mm).
- Do not bend more than 90 degrees.
- Do not bend the same tube more than 3 times.
If the unit shows an error code, look it up: Carrier Air Handler codes
Models
D5FUHAH24AAKD5FUHAH36AAKD5FUHAH60AAKEHKMD05KNEHKMD08KNEHKMD10KNEHKMD15KNEHKMD20KNEHKMD25KN
Source: D5FUHA installation instruction, p. 28-29. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.