Carrier Air Handler: Additional refrigerant charge for longer line sets (R-454B)
Additional refrigerant charge for longer line sets (R-454B) on a Carrier air handler: Only charge extra refrigerant when the pipe run is longer than the 25 ft (7.5 m) standard. Never mix refrigerant types, as this damages the equipment. Charge through the service port on the outdoor unit's low pressure valve. The page's Table 28 header is partly cut off, but the formula for the 3/8 in. liquid line is legible.
Applies to: D5FUHA with R-454B refrigerant, 3/8 in. (9.52 mm) liquid line
How to fix additional refrigerant charge for longer line sets (r-454b): step by step
- Measure the total installed liquid line length.
- Subtract the standard length of 25 ft (7.5 m).
- Multiply the difference by 65 g/m (0.7 oz/ft).
- Charge the result through the outdoor unit low pressure service port.
- Record the pipe length and additional charge (the test run checklist asks for both).
If the unit shows an error code, look it up: Carrier Air Handler codes
Models
D5FUHAH24AAKD5FUHAH36AAKD5FUHAH60AAKEHKMD05KNEHKMD08KNEHKMD10KNEHKMD15KNEHKMD20KNEHKMD25KN
More commissioning tips for air handler
Source: Carrier D5FUHA Installation Instructions, p. 61. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.