Carrier Air Conditioner: Condensate trap and secondary drain when unit is over living space
Condensate trap and secondary drain when unit is over living space on a Carrier air conditioner: If the unit sits in or above a living space where condensate overflow could cause damage, add a field-supplied external pan under the whole unit with a secondary condensate line and trap running into it. An alternative, where local code allows, is a separate 3/4 in (19 mm) condensate line with trap to a visible drain point. Tell the owner that flow from the secondary drain means the unit needs service. Fit a float switch to shut the unit off if the secondary pan water rises too high.
Applies to: DLFULA air conditioner condensate drain (Fig. 15 Trap)
How to fix condensate trap and secondary drain when unit is over living space: step by step
- Check whether the unit is in or above a living space where overflow could cause damage.
- Install a field-supplied external condensate pan under the entire unit if required.
- Run a secondary condensate line with an appropriate trap from the unit into the pan.
- Drain the external pan to a noticeable location.
- Where local code allows, use a separate 3/4 in (19 mm) condensate line with trap to a visible point instead of the pan.
- Install a float switch to shut the unit off if the secondary pan water gets too high.
- Tell the owner that secondary drain flow means the unit needs servicing.
If the unit shows an error code, look it up: Carrier Air Conditioner codes
More commissioning tips for air conditioner
Source: DLFULA Installation Instructions, p. 16. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.