Viessmann Mini-Split: Power and communication wiring between indoor and outdoor unit
Power and communication wiring between indoor and outdoor unit on a Viessmann mini-split: Main power is supplied to the outdoor unit. The field-supplied 14/3 cable carries four wires: two high-voltage AC, one communication and one ground. Wiring is polarity sensitive. Do not use BX cable. Disconnecting the outdoor unit also de-energizes the indoor unit.
Applies to: DLFSHC indoor and outdoor unit interconnect
How to fix power and communication wiring between indoor and outdoor unit: step by step
- Size wires per NEC or CEC and local codes, using the outdoor unit MCA and MOCP.
- Use 14/3 cable with four wires: two AC power, one communication, one ground.
- Keep the polarity of the indoor-to-outdoor wiring correct.
- Do not use BX cable.
- Where EMF interference causes communication faults, 14/2 stranded shielded wire may replace wires 2 and 3, with the shield grounded at the outdoor unit only.
- Make every connection tight and keep wires away from refrigerant tubing, the compressor and moving parts.
If the unit shows an error code, look it up: Viessmann Mini-Split codes
Models
DLFSHCH06XAKDLFSHCH09XAKDLFSHCH12XAJDLFSHCH12XAKDLFSHCH18XAKDLFSHCH24XAKDLFSHCH30XAKDLFSHCH36XAK
More other tips for mini-split
Source: DLFSHC installation instructions, p. 7. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.