Viessmann Boiler: Set Vitodens WB2B coding 00 to 00
Set Vitodens WB2B coding 00 to 00 on a Viessmann boiler: Coding 00 cannot be set to 0 directly. The Vitodens boiler pump keeps running unless this is done correctly.
Applies to: Vitodens 200 WB2B with Vitotronic 100 HC1
How to fix set vitodens wb2b coding 00 to 00: step by step
- Temporarily change coding 01 to 2 (multi-boiler). Listen for the click.
- Change coding 01 back to 1.
- Set address 34 to 23.
- Confirm coding 00 now reads 00.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
More commissioning tips for boiler
Source: Versatronik 300 Cascade Control technical, installation and configuration manual, p. 15. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.