Viessmann Boiler: Modbus RS-485 wiring and termination
Modbus RS-485 wiring and termination on a Viessmann boiler: Use COM 1 terminals A and B. Terminal naming differs between manufacturers, so A is the non-inverting (+) line and B is the inverting (-) line. The gateway has no termination resistor, only two weak 4.7 kOhm pull up/down bias resistors on the lines. Add termination at the network ends as the Modbus network requires.
Applies to: Versatronik 502 and 502D gateway, all listed controls
How to fix modbus rs-485 wiring and termination: step by step
- Connect the field Modbus wiring to COM 1 terminals A and B.
- Match A to the (+) non-inverting side and B to the (-) inverting side of the DDC network.
- Do not rely on the gateway for line termination; provide it on the network if needed.
If the unit shows an error code, look it up: Viessmann Boiler codes
More commissioning tips for boiler
Source: Versatronik 502 MODBUS manual, p. 8. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.