Updated · by Aurora Star Tech Inc.

Modbus RS-485 wiring on a Viessmann boiler: Use COM 1 terminals A and B for Modbus. A is the non-inverting (+) line and B is the inverting (-) line. Naming can differ between manufacturers, so check the DDC system. The gateway has no termination resistor, so handle termination at the network. Two 4.7 kOhm pull-up/pull-down bias resistors are on the lines.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Versatronik 502 and 502D MODBUS gateway

How to fix modbus rs-485 wiring: step by step

  1. Connect the DDC network to COM 1 terminals A and B on the gateway.
  2. Confirm A is (+) and B is (-) against the DDC system labelling.
  3. Add termination at the network end, because the gateway does not provide it.
  4. Confirm the Modbus device address is set on the rotary dial.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

More commissioning tips for boiler

Source: Versatronik 502 NR2 Modbus manual, p. 8. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.